SPECIFICATIONS
Operating Voltage Range: 9 to 28VDC Volts
Alarm Resistance 470ohm/1W
Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing
Operating Temperature Range: -10°C to 50°C (14°F to 122°F)
Dimensions: Length 140mm, Width 105mm, Depth 45mm
Weight: Net Weight 220g
OPERATION
The manual call points provide a textured finger-hold
area that includes Braille text. In addition to PUSH IN
and PULL DOWN text, there are arrows indicating how
to operate the station, provided for non-English-speaking
people.
Pushing in and then pulling down on the handle activates
the normally-open alarm switch. Once latched in the
down position, the word “ACTIVATED” appears at the
top in bright yellow, with a portion of the handle
protruding at the bottom as a visible flag.
Resetting the station is simple: insert the key, twist one
quarter-turn, then open the station’s front cover, causing
the spring-loaded operation handle to return to its original
position. The alarm switch can then be reset to its normal
(non-alarm) position manually (by hand) or by closing the
station’s front cover, which automatically resets the
switch.
Loop Design and Wiring
The fire alarm control panel Zone wire can be connected
to terminal loop (+), loop (-) unpolarized wire.
If the manual call point is in the end of the zone wire, a
5.6K resistance should be connected to terminal loop (+),
loop (-).
INSTALLATION
NOTE: All wiring must conform to applicable local
codes, ordinances, and regulations.
Mounting Indoor Wall
1. Attach mounting base to wall at 1.5 meter’s high.
2. Connect field wiring to terminals
3. To attach product to mounting base.
4. Secure product by tightening the one mounting screws
in the front of the product housing.